Ball Valves
Full-bore stainless ball valves from mini G1/8 CDU sizes through quick-connect straight and Tri-Clamp three-way variants to mechanically interlocked versions, all rated 16 bar with PTFE zero-leakage seats.
16 bar · 316LGerman-engineered stainless valves for closed cooling loops: automatic air vents, ball, butterfly, check and safety valves, strainers and flow instrumentation. HeTone distributes and supports the range across Asia.
Löwenauge Industry combines German engineering, from its office in Erlangen, with production in China, focused on one discipline: precise control of closed piping systems with zero-leakage technology. The company is ISO 9001:2015 certified and its Greater China operations centre ships within 30 days.
The brand made its name on automatic air-vent valves for liquid cooling. The VAC 71 side-exhaust series is presented as the first stainless-steel air vent developed specifically for data-center CDUs: a dry-closure design keeps coolant away from the vent opening so it cannot clog, and a rotation-resistant float keeps venting reliable even on vibrating equipment such as wind turbines.
Around the vents sits a complete stainless valve programme for CDU and rack-level cooling loops: full-bore and mini ball valves, interlocking and quick-connect variants, butterfly valves to DN200, low-cracking-pressure check valves, 300-mesh Y-strainers, resetting safety valves, and flow instrumentation up to an IO-Link electromagnetic flowmeter.
Full-bore stainless ball valves from mini G1/8 CDU sizes through quick-connect straight and Tri-Clamp three-way variants to mechanically interlocked versions, all rated 16 bar with PTFE zero-leakage seats.
16 bar · 316LFlanged DN50 to DN200 stainless butterfly valves with EPDM or Viton seats and bubble-tight shutoff, operated manually, pneumatically or electrically for CDU and facility mains.
DN50 – DN200316L and 304 check valves that open below 0.05 bar, sealing with EPDM, FKM or PTFE across threaded, flanged and Tri-Clamp connections to protect CDU and manifold circuits from backflow.
Opens ≤ 0.05 barStainless Y-strainers with a removable 300-mesh, 48 µm screen and a flow area two to three times the pipe section, catching weld slag and debris before it reaches pumps and cold plates.
300 mesh · PN10The Löwenauge speciality: VAC 71 side-exhaust and VA 73 top-exhaust vents release trapped air and microbubbles continuously, with a dry closure that keeps coolant off the opening.
Vents at 0.2 barSpring safety valves in copper or stainless steel with relief settings from 2.5 to 10 bar and precise reseating after the event, protecting CDU and rack loops from overpressure.
2.5 – 10 bar reliefStainless flow sensors covering 0.9 to 240 L/min with frequency and pulse outputs for continuous coolant flow monitoring across DN8 to DN32 lines.
0.9 – 240 L/minA compact all-in-one magmeter, DN6 to DN65, with PEEK liner, ±0.5% accuracy and IO-Link or Modbus RTU connectivity for precision loop measurement.
±0.5 % accuracyTrapped air and microbubbles cut cooling efficiency and can overheat hardware. Löwenauge air vents release them continuously, and the dry-closure principle means coolant never touches the vent opening, so it cannot clog or weep.
The first stainless air vent developed specifically for data-center CDUs. Side-exit venting for tight manifold spaces, with check-valve and ball-valve variants.
Vertical venting for the highest point of the loop, where air naturally collects. Stainless or nickel-plated copper bodies, with ball-valve service variants.
| Model | Body | Max. pressure | Vent opens | Temperature | Connection |
|---|---|---|---|---|---|
| VAC 71 | SUS 316L | 16 bar | 0.2 – 0.5 bar | -40 – 115 °C | G3/8 |
| VAC 71-Z | SUS 316L | 16 bar | 0.2 – 0.5 bar | -40 – 115 °C | With check valve R3/8 · R1/2 · G1/2 |
| VAC 71-B | SUS 316L | 16 bar | 0.2 bar | -40 – 115 °C | With ball valve G3/8 · G1/2 |
| VACI 71 | SUS 304 | 16 bar | 0.2 bar | -40 – 115 °C | G3/8 |
| VACI 71-Z | SUS 304 | 16 bar | 0.2 bar | -40 – 115 °C | With check valve R3/8 · R1/2 · G1/2 |
| VACI 71-B | SUS 304 | 16 bar | 0.2 bar | -40 – 115 °C | With ball valve G3/8 · G1/2 |
| Model | Body | Max. pressure | Vent opens | Temperature | Connection |
|---|---|---|---|---|---|
| VA 73 | SUS 316L | 16 bar | 0.2 bar | -40 – 115 °C | G3/8 |
| VAI 73 | SUS 304 | 16 bar | 0.2 bar | -40 – 115 °C | G3/8 |
| VA 73-B | SUS 316L | 16 bar | 0.2 bar | -40 – 115 °C | With ball valve G3/8 · G1/2 |
| Nickel-plated copper VAT 73 | CW617N | 16 bar | 0.2 bar | -30 – 115 °C | G3/8 |
| VAT 73-Z | CW617N | 16 bar | 0.2 bar | -30 – 115 °C | With check valve R3/8 · R1/2 · G1/2 |
| VAT 73-B | CW617N | 16 bar | 0.2 bar | -30 – 115 °C | With ball valve G3/8 · G1/2 |
Every shutoff, protection and filtration point of a CDU or rack cooling loop, in 304 and 316L stainless with zero-leakage seats, shown in official product photos.
Tap any product to see its full specifications
Full-bore shutoff for CDU, manifold and AI-server cooling loops. Tri-Clamp and weld-end three-piece bodies in 316L for easy in-line service.
Ultra-compact shutoff for high-density CDU layouts and sensor lines. Machined to DIN EN ISO 2768-1, every valve helium-tested to a leak rate under 2 grams per year.
Shutoff and quick coupling in one body: connect or open a line in seconds during installation and service, without draining the loop.
Tri-Clamp three-way routing with a no-dead-leg design that keeps coolant clean and flow resistance low — built for modular data-center deployment.
A mechanical interlock physically prevents mis-operation on critical loops — the valve cannot be opened or closed out of sequence.
Bubble-tight shutoff for CDU and facility mains from DN50 to DN200, operated manually, pneumatically or electrically.
Backflow protection that opens below 0.05 bar, so it costs the pump almost nothing. Threaded, flanged and Tri-Clamp connections protect CDU and manifold circuits.
Catches weld slag and debris before it reaches pumps and cold plates. The removable 300-mesh screen has a flow area two to three times the pipe section, so pressure drop stays low.
Spring safety valves that relieve overpressure and reseat precisely after the event. VS320 in stainless for CDU and rack loops; VS311/VS312 in copper for general industrial circuits.
| Model | Material | Connection | Pressure | Recommended for |
|---|---|---|---|---|
| KBV-304-M08 | SUS304 | G1/8 | 16 bar | Miniature sensor lines |
| KBV-316-M10 | SUS316L | G1/4 | 16 bar | Corrosive environments |
| KBV-304-M12 | SUS304 | G3/8 | 16 bar | Standard CDU applications |
| KBV-316-M15 | SUS316L | G1/2 | 16 bar | High-performance cooling loops |
From simple pulse sensors to a billing-grade electromagnetic meter with digital connectivity.
Pulse-output turbine sensing for continuous coolant monitoring, in stainless across six line sizes.
These are selected highlight SKUs, contact us for the full catalogue and custom cut sizes.
| Model | Type | Key Spec | Application |
|---|---|---|---|
| SS Ball Valve | Ball Valve | 316L, 16 bar, -40 – 120 °C | CDU, manifold and rack loops |
| KBV Mini Series | Ball Valve | G1/8 – G1/2, He-tested < 2 g/yr | Sensor lines, compact CDU layouts |
| Quick-Connect Straight | Ball Valve | 304/316L, 16 bar | Fast service connections |
| Quick-Connect 3-Way | Ball Valve | Tri-Clamp, low dead-leg | Modular data-center deployment |
| Interlocking Ball Valve | Ball Valve | Mechanical interlock, 316L | Fail-safe critical loops |
| SS Butterfly Valve | Butterfly Valve | DN50 – 200, 10 bar | CDU and facility mains |
| SS Check Valve | Check Valve | Opens ≤ 0.05 bar, 16/25 bar | Backflow protection at CDUs |
| SS Y-Strainer | Strainer | 300 mesh / 48 µm, PN10 | Debris capture ahead of pumps |