Brazed Plate Heat Exchangers
Copper-brazed SUS 316L / 304 plate packs from the compact B3-040 to the 800 kW B3-210, rated 30/45 bar design pressure across -160 to +225 °C, with weld, thread and flange connections.
5 – 800 kW
Copper-brazed plate heat exchangers from 5 to 800 kW: the liquid-to-liquid core of in-rack and in-row CDUs, engineered by Zhejiang Yinlun Machinery, a thermal-management manufacturer shipping 95 million heat exchangers a year. HeTone integrates Yinlun cores into the same loop as its pumps, piping, quick disconnects and coolants.
Zhejiang Yinlun Machinery Co., Ltd. was established in 1958 and brings 68 years of thermal-management and heat-exchanger expertise. A global leading provider of thermal solutions, Yinlun reached RMB 15 billion in revenue in 2025 and ships 95 million heat exchangers a year, with manufacturing bases across China, North America, Mexico, Poland and Malaysia: more than 10 overseas facilities and over 1,500 overseas staff for localized supply and fast lead times.
For AI data centers, that heat-transfer engineering goes into the liquid-cooling loop as copper-brazed plate heat exchangers, the liquid-to-liquid core where the IT loop hands its heat to facility water inside a CDU. Cores are developed forward: simulation modeling, performance testing and selection software, with innovative fin patterns, optimized flow distribution, anti-freezing design and lightweight, low-charge construction. HeTone pairs Yinlun cores with the pumps, piping, quick disconnects, coolants and leak control of its liquid-cooling loop portfolio, so CDU builders qualify the whole thermal path with one team.
Copper-brazed SUS 316L / 304 plate packs from the compact B3-040 to the 800 kW B3-210, rated 30/45 bar design pressure across -160 to +225 °C, with weld, thread and flange connections.
5 – 800 kWForward-engineered development: simulation modeling, performance testing and selection software match plate count and flow to your duty point, with innovative fin patterns and optimized flow distribution.
Selection softwareManufacturing across China, North America, Mexico, Poland and Malaysia, shipping 95 million heat exchangers a year, with anti-freezing design and lightweight, low-refrigerant-charge construction.
95M units / yearof thermal-management and heat-exchanger engineering since 1958
heat exchangers shipped annually across every application
revenue in 2025 as a global thermal-solutions leader
largest single brazed core, flanged for in-row CDU duty

Inside a CDU, the brazed plate heat exchanger is where the IT loop hands its heat to facility water. Corrugated stainless plates, vacuum-brazed with copper, form dozens of parallel channels in counterflow: high transfer area in a package small enough for rack-level cooling, with no gaskets to age or leak.

B3-040, B3-055M and G60 span 5 to 140 kW in slim packages sized for 4U and 5U in-rack CDUs. Copper pipe insert-weld and threaded connections from ½ to 1-7/8 in land directly on the CDU manifold, and anti-freezing design protects cores through cold starts and idle loops.

The B3-210 carries the same brazed construction to in-row CDU and facility duty: up to 800 kW and 2667 L/min per core, with DN65 to DN100 flange fittings and up to 300 plates in one pack. Feet-mounted, flanged, and ready to pair with pumps and grooved piping on the secondary loop.
Four cores cover 5 to 800 kW on overlapping ranges, so one family carries a design from compact in-rack CDUs to in-row and facility duty. Hover a band for flow and connection details.
All models: 30/45 bar design pressure, -160 to +225 °C design temperature, SUS 316L / 304 plates with copper brazing, weld and thread connections. Contact us for plate-count selection and datasheets.
| Model | Type | Key Spec | Application |
|---|---|---|---|
| B3-040 | Brazed plate heat exchanger | 5 – 40 kW, 33 – 333 L/min | Compact CDU cores |
| B3-055M | Brazed plate heat exchanger | 13 – 130 kW, 50 – 367 L/min | 4U/5U in-rack CDUs |
| G60 | Brazed plate heat exchanger | 15 – 140 kW, 50 – 367 L/min | In-rack CDUs |
| B3-210 | Brazed plate heat exchanger, flanged | 60 – 800 kW, 117 – 2667 L/min, DN65 – DN100 | In-row CDUs, facility loops |
Send us your heat load, flow rates and approach temperature, and we will size the brazed plate core and the loop around it.