Sensing Rope & Wire
Integrated high-flame-retardant sensor wire, UL94 V-0 and IP5X, that runs along manifolds and drip points. Detects the leak, and also reports a broken or unplugged line.
0.1 ml sensitivity
Liquid cooling puts coolant lines next to the most valuable silicon in the building. TCT's sensing ropes, thin-film plates and V4 controllers are the early-warning layer: they catch a leak from a 0.1 ml drop, flag a cut line, and report it upstream before it becomes an outage. HeTone is the authorized agent.
A liquid-cooling loop is only as safe as its ability to notice a drip. TCT (Thermal Control Technology, Shenzhen) builds that ability as a product: a flame-retardant sensing wire that runs along CDU manifolds, rack loops and every joint, plus thin-film plates for cold plates and flat surfaces. From as little as 0.04 ml, about six drops, the sensing line's resistance collapses far below the 255 kΩ alarm threshold, and the V4 controller reports leak or cut-line to your monitoring within seconds.
The current LC2-AD13 / YEC-SHTH(M) generation is an OCP-listed design with the segment's widest operating envelope: -20 to 70 °C, 5 to 95% RH, and 3 to 30 VDC supply, CE and RoHS certified, UL94 V-0 flame-retardant. HeTone integrates TCT detection into the same loop as its pumps, piping, bellows and coolants, so the whole thermal path, including its safety net, comes from one team.
Integrated high-flame-retardant sensor wire, UL94 V-0 and IP5X, that runs along manifolds and drip points. Detects the leak, and also reports a broken or unplugged line.
0.1 ml sensitivityA 59 × 84 × 0.2 mm film that detects water and conductive liquids on flat surfaces and cold plates: response within 2 seconds, over 65 wear cycles, series or parallel routing.
≤ 2 s responseThe controller behind the rope: 35.6 × 7.0 mm PCB in a 60 mm black-PVC shell, auto-reset after the hazard clears, dry-contact style outputs your BMS already understands.
Auto-resetThree moments in a machine room. Press one and watch what the module does, and what your monitoring hears.
Engineering note: leak on DO1, cut line on DO2, open-collector outputs your BMS reads directly. Full pinout in the datasheet.

The sensor wire watches for two failures, not one. Coolant on the line pulls DO1 low and the LED goes red. A broken or unplugged line pulls DO2 low, so a rope that can no longer protect you is itself an alarm. When the hazard is cleared, the module resets on its own, no manual re-arm.

Where a rope cannot reach, a 0.2 mm film can. The thin-film plate detects water and conductive liquids on flat surfaces in clean environments: under cold plates, below quick disconnects, in drip trays. Response inside 2 seconds, over 65 wear cycles, customizable outline and reusable after cleanup.

The fourth-generation module shrinks the shell from 80 to 60 mm around a 35.6 × 7.0 mm PCB, moves to black PVC, and holds craftsmanship tolerances: zero surface defects, zero burrs, TCT engraving on every shell. Small enough to disappear into the rack, finished like a product someone signs.
Measured on the sensing line: pick a fluid and a spill size. Even six drops collapse the line's resistance to a few kΩ, far below the 255 kΩ alarm threshold.
How it works: liquid collapses the sensing line's resistance, 0.04 ml measures 15.5 kΩ, far below the 255 kΩ alarm threshold. One drop is about 0.0067 ml.
| Feature | Traditional solutions | HeTone × TCT |
|---|---|---|
| Architecture | Fixed / standalone | ✓ Modular cable + sensor combo |
| Sensitivity | Fixed, low | ✓ Customizable, down to 0.1 ml |
| Safety rating | Standard | ✓ UL94 V-0 flame-retardant |
| Validation | Localized | ✓ CE, RoHS, OCP listed |
| Form factor | Bulky | ✓ Minimized 60 mm casing |
All parts CE and RoHS certified, on an OCP-listed supplier design, engineered for zero false alarms: tested through 70 °C and 90% RH for over eight hours continuously.
| Model | Type | Key Spec | Application |
|---|---|---|---|
| LC2-AD13 / YEC-SHTH(M) | Integrated sensor wire, V4 | UL94 V-0 · IP5X · -20 to 70 °C · 3 – 30 VDC | CDU manifolds, rack loops |
| Thin-film plate | Leakage sensing plate | 59 × 84 × 0.2 mm · ≤ 2 s response · > 65 cycles | Cold plates, flat surfaces |
| V4 module | Detection controller | 35.6 × 7.0 mm PCB · 60 mm shell · auto-reset | Every sensing line |
Tell us your loop layout, manifold runs and drip points, and we will spec rope lengths, plate positions and controller counts, with samples and datasheets from stock.