Five Solstice® fluids cover a data centre's whole cooling duty: room and precision air conditioning, air- and water-cooled chillers, heat pumps and two-phase liquid cooling on cold plates. HeTone supplies the range across Asia with safety-class guidance and selection support.

Honeywell Solstice products
5
Solstice® fluids for data centres
A2L + A1
both ASHRAE safety classes
<1
lowest GWP in the range
−78%
GWP vs R-410A (Solstice 454B)
Brand Overview

Honeywell Solstice® refrigerants are engineered for the room and precision air conditioning that data centres run on - and as chips grow hotter and denser, two-phase liquid cooling on Solstice fluids delivers uniform cooling with better heat rejection and lower pumping power. The range spans two ASHRAE safety classes: A2L where codes accept mildly flammable equipment and efficiency leads the specification, and nonflammable A1 where the safety case rules flammability out.

Each of the five fluids is positioned against a refrigerant the industry already runs. Solstice 454B replaces R-410A with matching capacity and a GWP 78% lower; ze, N15 and 513A give three exit paths from R-134a at three GWP levels; and zd replaces R-123 in low-pressure centrifugal chillers at a GWP of 1. Published GWP values run from 631 down to below 1 on the IPCC AR5 basis.

Solstice Advanced Materials was created through the 2025 spin-off of Honeywell's Advanced Materials business - the same fluorine chemistry, manufacturing network and Solstice platform, now a dedicated company. HeTone distributes the refrigerant range across Asia, from fluid selection and safety-class guidance through datasheets, SDS documentation and supply.

The Range

Five fluids, two safety classes.

Filter by ASHRAE class and the range narrows to match. GWP values are Solstice’s published IPCC AR5 figures.

5 fluids
01 A2L · Mildly flammable
Solstice® 454B (R-454B) cylinder

Solstice® 454B

R-454B
GWP 46778% lower than R-410A

The most optimized R-410A replacement: matching capacity, improved efficiency and minimal redesign for precision cooling and reversible heat pumps.

Zeotropic blend Glide 1.5 POE Replaces R-410A
02 A2L · Mildly flammable
Solstice® ze (R-1234ze) cylinder

Solstice® ze

R-1234ze
GWP <1ultra-low GWP vs R-134a

Ultra-low-GWP, energy-efficient alternative to R-134a for the air-cooled and water-cooled chillers and heat pumps that carry a data centre's base load.

Pure fluid (HFO) Glide 0 POE Replaces R-134a
03 A1 · Nonflammable
Solstice® zd (R-1233zd) cylinder

Solstice® zd

R-1233zd
GWP 199%+ lower than R-123

Nonflammable with a GWP of 1: better capacity and similar efficiency to R-123 in low-pressure centrifugal chillers and high-temperature heat pumps.

Pure fluid (HFO) Glide 0 Mineral oil Replaces R-123
04 A1 · Nonflammable
Solstice® N15 (R-515B) cylinder

Solstice® N15

R-515B
GWP 29377% lower than R-134a

A nonflammable azeotropic blend that matches R-1234ze capacity and efficiency, so it drops straight into any system designed around R-1234ze.

Azeotropic blend Glide 0 POE Replaces R-134a
05 A1 · Nonflammable
Solstice® 513A (R-513A) cylinder

Solstice® 513A

R-513A
GWP 63156% lower than R-134a

A zero-glide, nonflammable R-134a replacement approved by major equipment makers: matching capacity and efficiency with no system redesign.

Azeotropic blend Glide 0 POE Replaces R-134a
Product Series

Featured product families.

A2L - efficiency first

Solstice 454B and Solstice ze, mildly flammable per ASHRAE 34. The choice where codes already accept A2L equipment and energy efficiency leads the spec.

2 fluids · GWP 467 / <1

A1 - nonflammable

Solstice zd, N15 and 513A carry Class A1 for safety cases that rule out flammability, from centrifugal chillers to drop-in R-134a service.

3 fluids · GWP 1-631

Every cooling duty

Room and precision air conditioning, air- and water-cooled chillers, heat pumps, and two-phase liquid cooling on cold plates.

AC · chillers · cold plates
Global Warming Potential

Every GWP on one scale.

All five fluids plotted against the same axis, using Solstice’s published AR5 values. Two of them barely register — that is the point.

Solstice® 513AR-513A 631A1
Solstice® 454BR-454B 467A2L
Solstice® N15R-515B 293A1
Solstice® zdR-1233zd 1A1
Solstice® zeR-1234ze <1A2L
0175350525700

GWP = Global Warming Potential, IPCC 5th Assessment Report basis, as published on each Solstice product page. Reduction claims (−78% vs R-410A, −56% / −77% vs R-134a) are Solstice’s own figures.

Typical Properties

The full datasheet, fluid by fluid.

Published typical properties from each Solstice product page — physical data, temperature limits, safety and approvals. Pick a fluid.

General Information

Application
Buildings - Chillers - Comfort Cooling and HeatingBuildings - Residential/Light Commercial AC/Heat PumpsBuildings - Variable Refrigerant Flow (VRF) SystemsData Centers - Room and Precision Air ConditioningIndustrial Process Refrigeration – Chillers: Low or Medium Temperature
ASHRAE Number
R-454B
Brand
Solstice®
Glide
1.5
Refrigerant Class
HFO Blend
Refrigerant Type
Zeotropic blend
Replaces
R-410A
Substitutes
R-410A
Typical Lubricant
POE

Physical Properties

Appearance
Colorless
Composition
R-32 / R-1234yf (68.9% / 31.1%)
Critical Density
443.1 kg/m3
Critical Pressure
52.7 bar
Critical Volume
0.00226 m3/kg
Liquid Density
996.5 kg/m3 at 25 °C
Liquid Heat Capacity
1.80 kJ/kg·°K at 25 °C
Liquid Thermal Conductivity
105.4 mW/m·°K at 25 °C
Liquid Viscosity
114.8 µPa·sec at 25 °C
Lower Flammable Limit
0.303 kg/m³
Molecular Weight
62.6 kg/kmol
Vapor Density
50.7 kg/m3 at 25 °C
Vapor Heat Capacity
1.43 kJ/kg·°K at 25 °C
Vapor Pressure
1515.9 kPa at 25 °C
Vapor Thermal Conductivity
15.0 mW/m·°K at 25 °C
Vapor Viscosity
12.8 µPa·sec at 25 °C

Temperature

Boiling Point/Range
-50.9 °C-59.62 °F
Critical Temperature
170.6 °F / 77.0 °C

Safety & Environment

Flammable Range
11.25% (LFL), 22.00% (UFL)
Global Warming Potential
467 rev /5TH IPCC
Ozone Depletion Potential
0

Standards & Approvals

ASHRAE Safety Classification
A2L (Mildly flammable)
REACH Product Stewardship
Approved

Typical properties as published by Solstice Advanced Materials on each product page; not a specification. For engineering design, request the full technical datasheet and SDS through HeTone.

Replacement Paths

Start from the refrigerant you run today.

Every fluid in the range is positioned against an incumbent. Pick yours and the answer follows.

Solstice 454B is Solstice's most optimized R-410A replacement: matching capacity, improved efficiency and a GWP 78% lower, with minimal changes from an R-410A design.

Solstice Advanced Materials

Solstice Advanced Materials was created through the 2025 spin-off of Honeywell’s Advanced Materials business — the same fluorine chemistry, plants and Solstice® platform the industry has run on for a decade, now a dedicated company. HeTone supplies the range across Asia with selection, documentation and SDS support.

Product Data

Representative product data.

Measured values from our application engineering materials. Contact us for complete datasheets and lot-specific certificates.

Solstice refrigerants · published data

Fluid ASHRAE No. Type Replaces GWPAR5 ClassASHRAE 34 Glide Lubricant
Solstice 454B R-454B Zeotropic blend R-410A 467 A2L 1.5 POE
Solstice ze R-1234ze Pure fluid (HFO) R-134a <1 A2L 0 POE
Solstice zd R-1233zd Pure fluid (HFO) R-123 1 A1 0 Mineral oil
Solstice N15 R-515B Azeotropic blend R-134a 293 A1 0 POE
Solstice 513A R-513A Azeotropic blend R-134a 631 A1 0 POE

Values from HeTone application engineering materials, request official datasheets for design sign-off.