HydroCool canned-motor pumps for AI liquid cooling

Canned-motor liquid-cooling pumps from 3 W to 45 kW: μ, S, M and L platforms covering cold plates, 4U/5U in-rack CDUs and in-row CDUs, with native 800 V HVDC options. HeTone integrates HydroCool pumps into the same loop as its hoses, quick disconnects, coolants and leak control.

HydroCool products
Brand Overview

HydroCool Technology is the data-center liquid-cooling pump brand of Feilong Auto Components (FLAC), a Shenzhen-listed automotive thermal-management manufacturer founded in 1952 with more than 6,500 employees, 652 patents, and supplier awards from GM, BorgWarner, Daimler Trucks and Cummins. Established in 2025 in Wuhu, HydroCool applies that automotive pump heritage, including volume 800 V pump programs for Bosch and Cummins, to hyperscale AI cooling.

The canned-motor design seals the rotor inside the pumped coolant: no dynamic shaft seals, fluid self-lubricated silicon-carbide hydrodynamic bearings, and validated MTBF beyond 100,000 hours, in line with the zero-leakage direction of OCP ORV3 and Deschutes-generation CDU specifications. Four platforms span 3 W to 45 kW, from cold-plate μ-pumps to in-row CDU pumps, and HeTone pairs them with the hoses, quick disconnects, fittings, coolants and leak control of its liquid-cooling loop portfolio so CDU builders can qualify the whole wet path with one team.

Product Series

Featured product families.

L-Platform In-Row CDU Pumps

Canned motor pumps for in-row CDU duty from 10 to 45 kW: HP75H, HP15K and HP22K cover 500 to 1500 lpm, HP37K reaches 2000 lpm at 650 kPa, in AC 380–480 V and native HVDC 800 V builds with backpack-integrated VFD.

10 – 45 kW

S / M-Platform In-Rack CDU Pumps

Stainless-housing pumps for 4U and 5U in-rack CDUs, 300 W to 5 kW with water-cooled controllers, in DC 12, 24 and 48 V plus DC 800 V builds. The hot-swappable HP45H, 300 lpm at 400 kPa, is in development.

4U / 5U CDU

μ-Platform Component Pumps

Compact 3 to 200 W pumps in PPS housings for cold plates and liquid-assisted air cooling, running on DC 12 or 48 V for component-level and edge cooling loops.

3 W – 200 W
In Depth

A closer look.

HydroCool canned motor pump in a data center aisle

Sealed for zero leakage

In a canned motor pump the rotor spins inside the coolant itself, hermetically sealed with no dynamic shaft seal to wear or weep. Fluid self-lubrication and silicon-carbide hydrodynamic bearings remove the classic service items, targeting five years of operation without scheduled maintenance, and the design aligns with the zero-leakage mandate of Google's Deschutes-generation OCP CDU specification.

  • No dynamic shaft seals, validated MTBF beyond 100,000 hours
  • SiC hydrodynamic bearings, lubricated by the coolant itself
  • Motor heat is carried away by the coolant, no external fans, no PUE penalty
HydroCool HVDC 800 V canned motor pump with backpack VFD

Native 800 V HVDC, born in automotive

FLAC has shipped 1.5 to 6 kW 800 V pumps in volume to Bosch and Cummins, and HydroCool carries that platform into the data center. A backpack-integrated, water-cooled VFD rides on the pump and shares the 800 V DC busbar with the IT racks: current is halved versus 400 V for roughly 75% lower copper loss, and no separate AC drive cabinet is needed.

  • Backpack VFD with sensor-less FOC control from automotive programs
  • Runs directly on the 800 V DC busbar, no costly AC VFDs
  • Over/under-voltage, overcurrent, locked-rotor and dry-run protection
HydroCool pump platforms from micro pumps to in-row CDU pumps

Four platforms, 3 W to 45 kW

The matrix runs from μ-platform pumps for cold plates and liquid-assisted air cooling, through S and M in-rack CDU pumps, to L-platform machines moving up to 2000 lpm today, with the YZ280 canned series extending to 3750 lpm at 650 kPa, sampling in Q4 2026. Every platform is validated automotive-style: ISO 16750 electrical and environmental suites, OCP pressure-cycle and marathon durability, IPX7, salt spray and burst-pressure testing at an IATF 16949 plant.

  • μ, S, M and L platforms cover cold plate to in-row CDU duty
  • YZ280 canned pumps reach 3750 lpm at 650 kPa
  • Validated to ISO 16750 suites plus OCP pressure-cycle and marathon durability
Product Matrix

Four platforms, one matrix.

Every HydroCool pump positioned by flow rate and hydraulic point, from cold-plate μ-pumps to in-row CDU machines. Duty points follow the official specification pages.

Model Flow rate (lpm) kPa
μ-Platform Cold plate
HP16 2.75 lpm 80
HP70 10 lpm 150
S-Platform 4U in-rack CDU
HP300 20 lpm 300
HP500 40 lpm 340
HP750 50 lpm 355
HP10H 100 lpm 355
HP15H 150 lpm 370
M-Platform 4U or 5U in-rack CDU
HP20H01 150 lpm 545
HP30H01 185 lpm 510
HP20H02 200 lpm 360
HP30H02 300 lpm 370
HP35H 300 lpm 475
HP45H 300 lpm 400
L-Platform In-row CDU
HP75H 500 lpm 600
HP15K 1000 lpm 600
HP22K 1500 lpm 590
HP37K 2000 lpm 650
Hydraulic point (kPa)

Bar length is the hydraulic point each pump holds at its duty flow; the flow rate for that duty point is listed with each model.

Key Models

Pump platforms and models.

Flow and duty points from the HydroCool product matrix. Contact us for duty-point sizing, official datasheets and CDU integration support.

ModelTypeKey SpecApplication
HP16 μ-Pump 2.75 lpm, DC 12/48 V Cold plates, liquid-assisted air cooling
HP70 μ-Pump 10 lpm, DC 12/48 V Cold plates, liquid-assisted air cooling
HP300 S-Pump 20 lpm 4U in-rack CDU
HP500 S-Pump 40 lpm 4U in-rack CDU
HP750 S-Pump 50 lpm 4U in-rack CDU
HP10H S-Pump 100 lpm 4U in-rack CDU
HP15H S-Pump 150 lpm 4U in-rack CDU
HP20H01 M-Pump 150 lpm 4U/5U in-rack CDU
Applications

Where HydroCool products are used.

Sizing pumps for an in-rack or in-row CDU?

Send us your duty point, flow rate and pressure drop, and we will size the pump and match it to the rest of the loop.