Huba Control vortex flow sensors for precise, wear-free flow measurement

Swiss-made vortex flow sensors covering 0.5 to 240 l/min across DN 6 to 32, with no moving parts, response times down to 5 ms and drinking-water approvals. HeTone supports selection from loop architecture down to type number.

Huba Control products
7
vortex models
DN 6–32
nominal widths
0.5–240
l/min measuring range
< 1 %
accuracy, full scale
Brand Overview

The vortex flow sensors from Huba Control are based on the physical principle of the Kármán vortex street. They precisely measure the flow rate of low to medium viscosity process media, and their very fast response time of less than 5 ms provides continuously reliable flow values wherever fast, accurate measurement is required.

The range spans seven type families from 0.5 to 240 l/min in nominal widths DN 6 to 32, with housings in glass-fibre plastic, red brass, brass and stainless steel. R290-compatible versions and variants with integrated temperature measurement are available, and the 240 series is completely PFAS-free.

HeTone distributes the Huba Control vortex range across Asia with application engineering and selection support, from cooling-loop architecture down to the exact type number and connection.

Selector

What are you building?

Tap an application and the range narrows to the sensors Huba lists for it. Flow range, nominal widths and housing are shown on every card.

Application
7 of 7 models
Huba Control vortex flow sensor 200
200
0.5 – 150 l/min DN 6–25 Plastic
Heat pumpsHybrid heat pumpsPellet and gas heating systems
Huba Control vortex flow sensor 210
210
0.5 – 150 l/min DN 6–25 Plastic
Heat pumpsVAV systemsIn-Rack CDU
Huba Control vortex flow sensor 230
230
1.8 – 150 l/min DN 10–25 Red brass
Hygienic rinsing stationIndustrial automation
Huba Control vortex flow sensor 235
235
0.9 – 240 l/min DN 8–32 Brass
District heatingIndustrial automation
Huba Control vortex flow sensor 236
236
0.9 – 240 l/min DN 8–32 Brass
District heatingSolar heatingHygienic rinsing station
Huba Control vortex flow sensor 237
237
1.1 – 240 l/min DN 8–32 Stainless steel
AHUCDUIn-Rack CDU
Huba Control vortex flow sensor 240
240
0.5 – 150 l/min DN 6–25 Plastic
Product Series

Featured product families.

Plastic in-line — 200 / 210 / 240

Glass-fibre PA and PPS bodies for heating water, drinking water and water–glycol loops.

DN 6–25 · 0.5–150 l/min

Brass & red brass — 230 / 235 / 236

Corrosion-resistant metal bodies for potable water, district heating and industrial media.

DN 8–32 · up to 240 l/min

Stainless steel — 237

Full stainless construction for aggressive media, high temperatures and data-centre coolant loops.

DN 8–32 · CDU-ready
The range

Seven sensors, one measuring principle.

Product information and applications as published by Huba Control. Each model carries its own quote button.

Huba Control vortex flow sensor 200 200

Vortex flow sensor 200

The flow sensors of Type 200 are based on the principle of the Kármán vortex street. The vortex flow sensors are free of moving parts, making them resistant to contamination. They are also characterized by a low pressure drop and high measurement accuracy. Optional variants with an integrated temperature sensor are available.

Flow range
0.5 – 150 l/min
Nominal width DN
6, 8, 10, 15, 20, 25
Housing
PA6T/6I (40 % glass fibre)
Response time
> 5 ms
  • Low-cost product with very good accuracy
  • Temperature-insensitive measuring principle
  • Excellent media resistance (measuring element without media contact)
  • Wider operating temperature range
  • Low pressure loss
  • Dirt-insensitive measuring element
  • Temperature measurement directly in the medium optionally with PT1000 or NTC
  • Drinking water approvals KTW, W270, ACS, WRAS, UBA 1+

Applications

Heat pumpsHybrid heat pumpsPellet and gas heating systems
Request a quote

DN size, housing material and lead time confirmed by return.

Huba Control vortex flow sensor 210 210

Vortex flow sensor 210

The flow sensors of Type 210 offer a wide range of configuration options for electrical power supply and output interfaces. The vortex flow sensors are maintenance-free due to their design without moving parts, making them resistant to contamination. Moreover, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Optional variants with an integrated temperature sensor are available.

Flow range
0.5 – 150 l/min
Nominal width DN
6, 8, 10, 15, 20, 25
Housing
PA6T/6I (40 % glass fibre)
Response time
5 – 500 ms
  • Flow measurement optionally with voltage, current, pulse, or frequency output
  • Excellent media resistance (measuring element without media contact)
  • Optionally with integrated temperature measurement
  • Temperature-insensitive measuring principle
  • Large temperature operating range
  • Low pressure loss
  • Dirt-insensitive measuring element
  • Drinking water approvals KTW, W270, ACS, WRAS, UBA 1+

Applications

Heat pumpsVAV systemsIn-Rack CDUUltrafiltration systemIndustrial automation
Request a quote

DN size, housing material and lead time confirmed by return.

Huba Control vortex flow sensor 230 230

Vortex flow sensor 230

The flow sensors of Type 230 are based on the principle of the Kármán vortex street. They offer a wide range of configuration options for electrical power supply and output interfaces. The vortex flow sensors are maintenance-free due to their design without moving parts, making them resistant to contamination. Moreover, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Additionally, the Type 230 provides high mechanical stability thanks to its red brass housing. Optional variants with an integrated temperature sensor are available.

Flow range
1.8 – 150 l/min
Nominal width DN
10, 15, 20, 25
Housing
PA6T/6I (40 % glass fibre), Red brass
Response time
5 – 500 ms
  • Flow measurement optionally with voltage, current, pulse, or frequency output
  • Excellent media resistance (measuring element without media contact)
  • Optionally with integrated temperature measurement
  • Large temperature operating range
  • Low pressure loss
  • Dirt-insensitive measuring element
  • Drinking water approvals KTW, W270, ACS, WRAS

Applications

Hygienic rinsing stationIndustrial automation
Request a quote

DN size, housing material and lead time confirmed by return.

Huba Control vortex flow sensor 235 235

Vortex flow sensor 235

The flow sensors of Type 235 are based on the principle of the Kármán vortex street. They differ from their counterpart, the Type 200, through their brass housing. The vortex flow sensors are free of moving parts, making them resistant to contamination. Furthermore, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Optional variants with an integrated temperature sensor are available.

Flow range
0.9 – 240 l/min
Nominal width DN
8, 10, 15, 20, 25, 32
Housing
Brass (CuZn21Si3P), PA6T/6I (40 % glass fibre)
Response time
> 5 ms
  • OEM product with very good accuracy
  • Temperature-insensitive measuring principle
  • Excellent media resistance (measuring element without media contact)
  • Wider operating temperature range
  • Low pressure loss
  • Dirt-insensitive measuring element
  • Temperature measurement directly in the medium optionally with PT1000 or NTC
  • Drinking water approvals ACS, WRAS

Applications

District heatingIndustrial automation
Request a quote

DN size, housing material and lead time confirmed by return.

Huba Control vortex flow sensor 236 236

Vortex flow sensor 236

The flow sensors of Type 236 are based on the principle of the Kármán vortex street. They differ from their counterpart, the Type 210, through their brass housing. The vortex flow sensors of Type 236 offer a wide range of configuration options for electrical power supply and output interfaces. Due to their maintenance-free design without moving parts, the sensors are resistant to contamination. Furthermore, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Optional variants with an integrated temperature sensor are available.

Flow range
0.9 – 240 l/min
Nominal width DN
8, 10, 15, 20, 25, 32
Housing
Brass (CuZn21Si3P), PA6T/6I (40 % glass fibre)
Response time
5 – 500 ms
  • Temperature-insensitive measuring principle
  • Excellent media resistance (measuring element without media contact)
  • Optionally with temperature measurement
  • Low pressure loss with high measurement accuracy
  • Dirt-insensitive measuring element
  • Temperature measurement directly in the medium
  • Drinking water approvals KTW, W270, ACS, WRAS, UBA 1+
  • High measurement accuracy

Applications

District heatingSolar heatingHygienic rinsing station
Request a quote

DN size, housing material and lead time confirmed by return.

Huba Control vortex flow sensor 237 237

Vortex flow sensor 237

Type 237 flow sensors operate according to the vortex principle, which is based on the Kármán vortex street. This non-mechanical measuring method enables precise and wear-free flow measurement without recalibration. The robust Stainless steel construction ensures high long-term stability and reliability, even in demanding environments. The sensor is designed for Medium temperatures from -15 to +125 °C and is suitable for applications ranging from cryogenic cooling to high temperature processes, such as in injection moulding plants. Integration into existing systems is greatly simplified by the M12x1 connector with IP65 and the plug-and-play design. The type 237 was developed for OEM applications that require precise, maintenance-free and long-term stable flow measurement.

Flow range
1.1 – 240 l/min
Nominal width DN
8, 10, 15, 20, 25, 32
Housing
Stainless steel
Response time
5 – 500 ms
  • Measuring element without media contact for maximum resistance
  • Optional temperature measurement of the medium
  • Low pressure loss with high measurement accuracy
  • Dirt-resistant design of the measuring element
  • Various output signal options
  • Electrical connection M12x1 with IP65

Applications

AHUCDUIn-Rack CDU
Request a quote

DN size, housing material and lead time confirmed by return.

Huba Control vortex flow sensor 240 240

Vortex flow sensor 240

The flow sensors of Type 240 are based on the vortex principle and deliver reliable measurement results for liquid media with varying specific viscosities – from antifreeze to drinking water. They operate without moving parts, ensuring long service life and high accuracy. These sensors are ideal for precise and stable flow measurements, even under challenging conditions. The Type 240 stands out due to its exceptional resistance to high system pressures and media temperatures. It offers excellent accuracy and outstanding leak tightness. Covering a wide range of applications, it is suitable for small diameters, such as precise measurements in DN 6 pipelines, as well as large diameters in industrial processes. Its compact design allows for direct mounting on the manifold, ensuring optimal space utilization.

Flow range
0.5 – 150 l/min
Nominal width DN
6, 8, 10, 15, 20, 25
Housing
PPS (40 % glass fibre)
Response time
800 ms (t90)
  • Wear-free and long-term stable sensor design
  • Rugged design for system pressure up to 16 bar
  • Up to 100 bar (pressure peaks)
  • Media temperature measurement (optional)
  • Hydrolysis-resistant sensor design
  • Drinking water approvals
  • UL 61010-1
  • High long-term stability

Applications

Huba lists no dedicated application pages for the 240. Its approved media are Drinking water, Heating water with standard additives, Water-glycol mixtures, Other media on request.

Request a quote

DN size, housing material and lead time confirmed by return.

Why vortex

No moving parts, no compromises on accuracy.

The vortex flow sensors from Huba Control are based on the physical principle of the Kármán vortex street. They precisely measure the flow rate of low to medium viscosity Process media in a wide range of applications.

01

Almost free pipe cross-section: Ideal for applications where maximum energy efficiency and performance are required, as the low pressure loss has little impact on the efficiency of the overall system.

02

Long-term stability, no zero-point drift: Stable measured values over the entire lifespan thanks to low-maintenance and long-life operation.

03

Very robust measuring principle: Reliable function even with severe temperature fluctuations.

04

Integrated temperature measurement: Automatic viscosity compensation ensures permanently precise measurement data - regardless of temperature fluctuations in the medium.

Encapsulated sensor element: vortex detection without medium contact

The encapsulated vortex detection ensures permanently precise flow measurement by completely separating the sensor from the medium. This design minimises deposits, offers high chemical resistance and ensures long-term stable measurement performance.

Housing

The right housing: protective shield against medium and time.

The housing material is a decisive factor for lifespan and reliability. Huba flow sensors are available in plastic, Stainless steel, brass and red brass - suitable for different media and operating conditions.

Plastic

DN 6–25

For applications with water and non-aggressive media, e.g. in building services engineering. Not suitable for high temperatures or aggressive chemicals (DN 6 - 25).

Red brass

DN 10–25

Highly corrosion-resistant, preferably for drinking water applications and heating systems. Suitable for medium pressures and temperatures (DN 10 - 25).

Brass

DN 8–32

Robust, versatile and durable. Frequently used in building services and for neutral Process media. Not recommended for aggressive media (DN 8 - 32).

Stainless steel

DN 8–32

For aggressive media, high temperatures and pressures. Used in chemicals, cooling systems and the food industry where maximum resistance is required (DN 8 - 32).

Data centre

Sensors for cooling applications in data centres.

Huba pressure and flow sensors are the optimal choice for cooling devices that use air and/or process media in data centres, such as CRAC, CDU and in-rack CDU systems. They ensure reliable and precise measurement data, which enables optimal and efficient operation of the cooling and filtration systems.

CRAC

Computer room air conditioning

Huba covers CRAC with differential pressure switches (types 604 and 699) rather than vortex flow sensors.

CDU

Coolant distribution unit

In-Rack CDU

In-rack coolant distribution

Circulation cooler

Closed-loop circulation cooling

Served by Huba pressure sensors (types 520 and 560); no vortex flow sensor is listed.

Two of the seven vortex sensors carry a data centre duty: the 237 on CDU and in-rack CDU, the 210 on in-rack CDU. The remaining data centre positions in Huba’s own application notes are held by pressure sensors and differential pressure switches, which sit outside this range.

Request a quote

Measuring a loop? Tell us the duty.