Huba Control vortex flow sensors for precise, wear-free flow measurement
Swiss-made vortex flow sensors covering 0.5 to 240 l/min across DN 6 to 32, with no moving parts, response times down to 5 ms and drinking-water approvals. HeTone supports selection from loop architecture down to type number.
The vortex flow sensors from Huba Control are based on the physical principle of the Kármán vortex street. They precisely measure the flow rate of low to medium viscosity process media, and their very fast response time of less than 5 ms provides continuously reliable flow values wherever fast, accurate measurement is required.
The range spans seven type families from 0.5 to 240 l/min in nominal widths DN 6 to 32, with housings in glass-fibre plastic, red brass, brass and stainless steel. R290-compatible versions and variants with integrated temperature measurement are available, and the 240 series is completely PFAS-free.
HeTone distributes the Huba Control vortex range across Asia with application engineering and selection support, from cooling-loop architecture down to the exact type number and connection.
What are you building?
Tap an application and the range narrows to the sensors Huba lists for it. Flow range, nominal widths and housing are shown on every card.







No vortex sensor covers that combination. Tell us the duty and we will size it from the wider Huba range.
Featured product families.
Plastic in-line — 200 / 210 / 240
Glass-fibre PA and PPS bodies for heating water, drinking water and water–glycol loops.
DN 6–25 · 0.5–150 l/minBrass & red brass — 230 / 235 / 236
Corrosion-resistant metal bodies for potable water, district heating and industrial media.
DN 8–32 · up to 240 l/minStainless steel — 237
Full stainless construction for aggressive media, high temperatures and data-centre coolant loops.
DN 8–32 · CDU-readySeven sensors, one measuring principle.
Product information and applications as published by Huba Control. Each model carries its own quote button.
200
Vortex flow sensor 200
The flow sensors of Type 200 are based on the principle of the Kármán vortex street. The vortex flow sensors are free of moving parts, making them resistant to contamination. They are also characterized by a low pressure drop and high measurement accuracy. Optional variants with an integrated temperature sensor are available.
- Flow range
- 0.5 – 150 l/min
- Nominal width DN
- 6, 8, 10, 15, 20, 25
- Housing
- PA6T/6I (40 % glass fibre)
- Response time
- > 5 ms
- Low-cost product with very good accuracy
- Temperature-insensitive measuring principle
- Excellent media resistance (measuring element without media contact)
- Wider operating temperature range
- Low pressure loss
- Dirt-insensitive measuring element
- Temperature measurement directly in the medium optionally with PT1000 or NTC
- Drinking water approvals KTW, W270, ACS, WRAS, UBA 1+
Applications
Heat pumps
Hybrid heat pumps
Pellet and gas heating systemsDN size, housing material and lead time confirmed by return.
210
Vortex flow sensor 210
The flow sensors of Type 210 offer a wide range of configuration options for electrical power supply and output interfaces. The vortex flow sensors are maintenance-free due to their design without moving parts, making them resistant to contamination. Moreover, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Optional variants with an integrated temperature sensor are available.
- Flow range
- 0.5 – 150 l/min
- Nominal width DN
- 6, 8, 10, 15, 20, 25
- Housing
- PA6T/6I (40 % glass fibre)
- Response time
- 5 – 500 ms
- Flow measurement optionally with voltage, current, pulse, or frequency output
- Excellent media resistance (measuring element without media contact)
- Optionally with integrated temperature measurement
- Temperature-insensitive measuring principle
- Large temperature operating range
- Low pressure loss
- Dirt-insensitive measuring element
- Drinking water approvals KTW, W270, ACS, WRAS, UBA 1+
Applications
Heat pumps
VAV systems
In-Rack CDU
Ultrafiltration system
Industrial automationDN size, housing material and lead time confirmed by return.
230
Vortex flow sensor 230
The flow sensors of Type 230 are based on the principle of the Kármán vortex street. They offer a wide range of configuration options for electrical power supply and output interfaces. The vortex flow sensors are maintenance-free due to their design without moving parts, making them resistant to contamination. Moreover, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Additionally, the Type 230 provides high mechanical stability thanks to its red brass housing. Optional variants with an integrated temperature sensor are available.
- Flow range
- 1.8 – 150 l/min
- Nominal width DN
- 10, 15, 20, 25
- Housing
- PA6T/6I (40 % glass fibre), Red brass
- Response time
- 5 – 500 ms
- Flow measurement optionally with voltage, current, pulse, or frequency output
- Excellent media resistance (measuring element without media contact)
- Optionally with integrated temperature measurement
- Large temperature operating range
- Low pressure loss
- Dirt-insensitive measuring element
- Drinking water approvals KTW, W270, ACS, WRAS
Applications
Hygienic rinsing station
Industrial automationDN size, housing material and lead time confirmed by return.
235
Vortex flow sensor 235
The flow sensors of Type 235 are based on the principle of the Kármán vortex street. They differ from their counterpart, the Type 200, through their brass housing. The vortex flow sensors are free of moving parts, making them resistant to contamination. Furthermore, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Optional variants with an integrated temperature sensor are available.
- Flow range
- 0.9 – 240 l/min
- Nominal width DN
- 8, 10, 15, 20, 25, 32
- Housing
- Brass (CuZn21Si3P), PA6T/6I (40 % glass fibre)
- Response time
- > 5 ms
- OEM product with very good accuracy
- Temperature-insensitive measuring principle
- Excellent media resistance (measuring element without media contact)
- Wider operating temperature range
- Low pressure loss
- Dirt-insensitive measuring element
- Temperature measurement directly in the medium optionally with PT1000 or NTC
- Drinking water approvals ACS, WRAS
Applications
District heating
Industrial automationDN size, housing material and lead time confirmed by return.
236
Vortex flow sensor 236
The flow sensors of Type 236 are based on the principle of the Kármán vortex street. They differ from their counterpart, the Type 210, through their brass housing. The vortex flow sensors of Type 236 offer a wide range of configuration options for electrical power supply and output interfaces. Due to their maintenance-free design without moving parts, the sensors are resistant to contamination. Furthermore, they are characterized by a low pressure drop and exceptionally high measurement accuracy. Optional variants with an integrated temperature sensor are available.
- Flow range
- 0.9 – 240 l/min
- Nominal width DN
- 8, 10, 15, 20, 25, 32
- Housing
- Brass (CuZn21Si3P), PA6T/6I (40 % glass fibre)
- Response time
- 5 – 500 ms
- Temperature-insensitive measuring principle
- Excellent media resistance (measuring element without media contact)
- Optionally with temperature measurement
- Low pressure loss with high measurement accuracy
- Dirt-insensitive measuring element
- Temperature measurement directly in the medium
- Drinking water approvals KTW, W270, ACS, WRAS, UBA 1+
- High measurement accuracy
Applications
District heating
Solar heating
Hygienic rinsing stationDN size, housing material and lead time confirmed by return.
237
Vortex flow sensor 237
Type 237 flow sensors operate according to the vortex principle, which is based on the Kármán vortex street. This non-mechanical measuring method enables precise and wear-free flow measurement without recalibration. The robust Stainless steel construction ensures high long-term stability and reliability, even in demanding environments. The sensor is designed for Medium temperatures from -15 to +125 °C and is suitable for applications ranging from cryogenic cooling to high temperature processes, such as in injection moulding plants. Integration into existing systems is greatly simplified by the M12x1 connector with IP65 and the plug-and-play design. The type 237 was developed for OEM applications that require precise, maintenance-free and long-term stable flow measurement.
- Flow range
- 1.1 – 240 l/min
- Nominal width DN
- 8, 10, 15, 20, 25, 32
- Housing
- Stainless steel
- Response time
- 5 – 500 ms
- Measuring element without media contact for maximum resistance
- Optional temperature measurement of the medium
- Low pressure loss with high measurement accuracy
- Dirt-resistant design of the measuring element
- Various output signal options
- Electrical connection M12x1 with IP65
Applications
AHU
CDU
In-Rack CDUDN size, housing material and lead time confirmed by return.
240
Vortex flow sensor 240
The flow sensors of Type 240 are based on the vortex principle and deliver reliable measurement results for liquid media with varying specific viscosities – from antifreeze to drinking water. They operate without moving parts, ensuring long service life and high accuracy. These sensors are ideal for precise and stable flow measurements, even under challenging conditions. The Type 240 stands out due to its exceptional resistance to high system pressures and media temperatures. It offers excellent accuracy and outstanding leak tightness. Covering a wide range of applications, it is suitable for small diameters, such as precise measurements in DN 6 pipelines, as well as large diameters in industrial processes. Its compact design allows for direct mounting on the manifold, ensuring optimal space utilization.
- Flow range
- 0.5 – 150 l/min
- Nominal width DN
- 6, 8, 10, 15, 20, 25
- Housing
- PPS (40 % glass fibre)
- Response time
- 800 ms (t90)
- Wear-free and long-term stable sensor design
- Rugged design for system pressure up to 16 bar
- Up to 100 bar (pressure peaks)
- Media temperature measurement (optional)
- Hydrolysis-resistant sensor design
- Drinking water approvals
- UL 61010-1
- High long-term stability
Applications
Huba lists no dedicated application pages for the 240. Its approved media are Drinking water, Heating water with standard additives, Water-glycol mixtures, Other media on request.
DN size, housing material and lead time confirmed by return.
No moving parts, no compromises on accuracy.
The vortex flow sensors from Huba Control are based on the physical principle of the Kármán vortex street. They precisely measure the flow rate of low to medium viscosity Process media in a wide range of applications.
Almost free pipe cross-section: Ideal for applications where maximum energy efficiency and performance are required, as the low pressure loss has little impact on the efficiency of the overall system.
Long-term stability, no zero-point drift: Stable measured values over the entire lifespan thanks to low-maintenance and long-life operation.
Very robust measuring principle: Reliable function even with severe temperature fluctuations.
Integrated temperature measurement: Automatic viscosity compensation ensures permanently precise measurement data - regardless of temperature fluctuations in the medium.
Encapsulated sensor element: vortex detection without medium contact
The encapsulated vortex detection ensures permanently precise flow measurement by completely separating the sensor from the medium. This design minimises deposits, offers high chemical resistance and ensures long-term stable measurement performance.
The right housing: protective shield against medium and time.
The housing material is a decisive factor for lifespan and reliability. Huba flow sensors are available in plastic, Stainless steel, brass and red brass - suitable for different media and operating conditions.
Plastic
DN 6–25For applications with water and non-aggressive media, e.g. in building services engineering. Not suitable for high temperatures or aggressive chemicals (DN 6 - 25).
Red brass
DN 10–25Highly corrosion-resistant, preferably for drinking water applications and heating systems. Suitable for medium pressures and temperatures (DN 10 - 25).
Brass
DN 8–32Robust, versatile and durable. Frequently used in building services and for neutral Process media. Not recommended for aggressive media (DN 8 - 32).
Stainless steel
DN 8–32For aggressive media, high temperatures and pressures. Used in chemicals, cooling systems and the food industry where maximum resistance is required (DN 8 - 32).
Sensors for cooling applications in data centres.
Huba pressure and flow sensors are the optimal choice for cooling devices that use air and/or process media in data centres, such as CRAC, CDU and in-rack CDU systems. They ensure reliable and precise measurement data, which enables optimal and efficient operation of the cooling and filtration systems.
CRAC
Computer room air conditioningHuba covers CRAC with differential pressure switches (types 604 and 699) rather than vortex flow sensors.
CDU
Coolant distribution unitIn-Rack CDU
In-rack coolant distributionCirculation cooler
Closed-loop circulation coolingServed by Huba pressure sensors (types 520 and 560); no vortex flow sensor is listed.
Two of the seven vortex sensors carry a data centre duty: the 237 on CDU and in-rack CDU, the 210 on in-rack CDU. The remaining data centre positions in Huba’s own application notes are held by pressure sensors and differential pressure switches, which sit outside this range.
Request a quoteMeasuring a loop? Tell us the duty.
Send the medium, flow range, line size and output signal you need, and we will confirm the right vortex sensor and availability from Huba Control’s Swiss production.